Hands-on tutorial

Tutorials · Fibre & GPON

How to Design a Fibre Backbone for a Campus or Multi-Building Site

Connect buildings with a resilient fibre backbone: star or ring topology, dual routes, fibre counts, core placement, redundant uplinks and documentation.

Advanced11 min7 steps

Before you start

  • A site map with buildings and existing ducts
  • The number of users and services per building
  • The location of the main data room

Step by step

  1. Choose the core location

    Place the core in the main data room with the best power, cooling and physical security.

  2. Pick a topology

    A star (each building to the core) is simple; a ring or dual star adds resilience. For critical sites, give each building two fibre routes on different paths.

  3. Size fibre counts

    Plan the links needed today, add spares generously (12–24 fibres per building is common), and remember fibre is cheap compared with digging.

  4. Use single-mode fibre

    Single-mode supports long distances and future speeds between buildings.

  5. Design the uplinks

    Connect each building's distribution switches to the core with two uplinks on separate fibres, using LACP or M-LAG, at 10G or more.

  6. Protect against loops and failures

    Use routed links or rapid ring protection, and test failover by disconnecting each path.

  7. Document everything

    Record routes, manholes, splice points, fibre allocations and test results.

Pro tips

  • Avoid running both routes through the same duct or bridge.
  • Leave slack loops in manholes for future repairs.
  • Keep a stock of spare patch cords and optics.