How to Size UPS Backup Power for PoE Switches, Cameras and Access Points
Keep cameras recording and Wi-Fi running through power cuts: calculate the load of PoE switches and recorders, choose UPS capacity and runtime, and test it.
Before you start
- The PoE draw of each switch (from its dashboard) plus its own consumption
- The power of NVRs, gateways and other rack equipment
- The runtime you need during an outage
Step by step
Measure the real load
For each PoE switch, add the PoE power actually delivered (shown on the switch) and the switch's own consumption from its datasheet. Add the NVR, gateway, and any other equipment on the UPS.
show poe power-budgetAdd headroom
Add 25–30% for future devices and for night-time infrared, which raises camera power.
Convert to VA
UPS units are rated in VA and watts. Choose a model whose watt rating is above your load. Running a UPS near 100% shortens its runtime and life.
Choose the runtime
Use the manufacturer's runtime tables for your load. For longer runtimes, add external battery packs or plan a generator, with the UPS covering the switch-over.
Use an online UPS for critical sites
Online (double-conversion) UPS units give clean power continuously and suit server rooms and outdoor cabinets with unstable supply. Line-interactive units suit offices with good mains power.
Monitor and shut down cleanly
Connect the UPS to the network (SNMP card) so you get alerts for power loss and low battery, and so NVRs and servers shut down cleanly before batteries run out.
Test every year
Unplug the mains in a maintenance window and time the runtime. Replace batteries when runtime drops noticeably, usually every three to five years.
Commands are generic, industry-standard examples. Exact syntax and menu names vary by model and firmware; check your device's manual on the Documentation page.
Pro tips
- Put PoE switches for cameras and access points on the UPS, not only the core.
- Outdoor cabinets need temperature-rated batteries; heat shortens battery life.
- Label which circuits and devices each UPS feeds.
FAQ
Frequently asked questions
Example: two 24-port PoE switches delivering 250 W each, plus a 60 W NVR?
About 2 × (250 + 40) + 60 = 640 W. With 30% headroom, plan for at least 830 W and a UPS rated around 1,000 W or more, then check the runtime table.
Can I put a UPS behind another UPS?
It is not recommended; the downstream UPS may see the upstream output as poor power.
Keep learning
Related guides
Choose the right PoE standard
Read more →PoE budget guide
Read more →Build an industrial switch cabinet
Read more →How to Use PoE Scheduling and Remote Power-Cycling
Save energy by switching PoE off outside business hours, and reboot a frozen camera or access point remotely.
Read more →How to Troubleshoot PoE Devices That Won't Power Up or Keep Rebooting
A systematic checklist for cameras and access points that stay dark, flicker or reboot at night.
Read more →How to Choose the Right PoE Standard (802.3af, 802.3at or 802.3bt) for Each Device
Match every IP camera, access point and phone to the right PoE class, check the switch port and the total budget, and avoid devices that reboot or never power up.
Read more →Stuck on a step?
Ask Navijin technical support or an authorised partner for help with your configuration.