Hands-on tutorial
Tutorials · Monitoring
How to Monitor Server Room Temperature, Humidity, Power and Doors
Catch overheating, leaks, power problems and unauthorised access in server rooms and network cabinets before equipment fails, with sensors and alerts.
Before you start
- Temperature and humidity sensors (network or SNMP-capable)
- A UPS with a network card
- A monitoring system that sends alerts
Step by step
Place temperature sensors correctly
Measure at the front (intake) of racks at the top, middle and bottom, not in the room corner. The intake temperature is what equipment experiences.
Set thresholds
A common target for equipment intake air is about 18–27 °C. Alert as a warning above 27 °C and critical above about 32 °C, or follow your equipment's limits.
Monitor humidity and leaks
Keep relative humidity in a moderate range to avoid static and condensation. Put a water leak sensor under air conditioners and near pipes.
Monitor power
Poll the UPS for input power, load, battery state and runtime. Alert on mains failure and low runtime.
Monitor doors and cabinets
Door contacts on the room and on outdoor or unattended cabinets show when they are opened. Combine with a camera for evidence.
Use device sensors too
Switches and servers report internal temperatures and fan status by SNMP. A rising internal temperature often warns before the room sensor does.
show environmentTest the alerts
Warm a sensor with your hand or open a door, and check that the alert reaches the right people.
Commands are generic, industry-standard examples. Exact syntax and menu names vary by model and firmware; check your device's manual on the Documentation page.
Pro tips
- Keep blanking panels in empty rack units so hot air does not recirculate.
- Graph temperatures over time to spot failing air conditioning early.
- Remote cabinets in hot climates need sensors more than server rooms do.
FAQ
Frequently asked questions
Is the room thermostat enough?
No. It measures one point, often far from the racks, and does not alert anyone when it is too hot.
What temperature is too hot for a switch?
Check the datasheet's operating range. Most commercial switches are rated to about 40–50 °C ambient; industrial models go higher.
Keep learning
Related guides
UPS backup power for PoE
Read more →SNMP and syslog monitoring
Read more →Network alerts by email and webhook
Read more →How to Monitor Your Network With SNMP and Syslog
Know about failures before users call: collect interface statistics with SNMPv3 and central logs with syslog.
Read more →How to Synchronise Time on Network Devices With NTP
Accurate clocks are essential for logs, certificates, schedules and CCTV evidence. Configure NTP everywhere in minutes.
Read more →How to Back Up and Restore Network Device Configurations
A configuration backup turns a failed device into a quick swap. Set up regular backups and test a restore.
Read more →Stuck on a step?
Ask Navijin technical support or an authorised partner for help with your configuration.